Watch a fault get caught

This is the pipeline running, live, on simulated data. A contactor switches a large motor on; something goes wrong; the tool measures it and decides pass or fail against a written specification.

Drag it. A bigger transformer holds the voltage up — and flips the verdict.
1 — where the data comes from

The machine

A contactor is a big switch. An electromagnet (its “coil”) pulls it closed and holds it there. Closing it makes the motor gulp a huge surge of current for a moment.

Coil voltage 24.0 V
Current draw 0.0 A
supply motor coil
OPEN
2 — what the tool does

The check

The tool reads both values several times a second over the network, then looks only at the moment that actually matters.

The written rule: while current is above 60 A, coil voltage must never fall below 20 V.
20 V limit
Samples inside the window 0
Lowest voltage seen there —
3 — what comes out

The verdict

At the end of each run the tool writes a report a colleague can read in thirty seconds — the number measured, the limit, and the gap.

…
waiting for the surge
Test caseTC-001
Measured minimum—
Specification≥ 20.0 V
Margin—

Run in progress…

Why this matters, in plain words

When the motor surges, it drags the whole supply down for a moment — including the small voltage feeding the contactor's own coil. If that dips too far, the electromagnet lets go. The switch chatters or drops out, the motor stops, and the line halts for a reason nobody can see afterwards.

It is easy to miss, because everything looks perfectly normal a second later. That is the point of measuring against a written limit instead of watching a graph: the tool checks the exact two seconds that matter and writes down what it found.

This page simulates the data. The real tool reads it from a PLC over OPC UA, a standard industrial protocol — and a browser cannot speak that, which is exactly why this is a simulation.